Serviceline Information

Sales phone: 0161 622 6309
Tech phone: 0161 622 6313
Fax: 0161 624 6537


  • 115/230 V AC supply
  • Output 24 V DC, 500 mA
  • Electronic short circuit protection
  • Power Rail connection

Datasheet as PDF in following languages:


Technical Data: KFA6-STR-1.24.500

Supply
Connectionterminals 14, 15
Rated voltage90 ... 253 V AC , 48 ... 63 Hz
Power loss2.5 W
Output
ConnectionPower Rail or terminals 7+, 8-
Current500 mA at 60 °C (140 °F) , permanent short-circuit protection (electronic)
Voltage24 V ± 0.5 V
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Low voltage
Directive 2006/95/ECEN 50178:1997
Conformity
Insulation coordinationEN 50178
Electrical isolationEN 50178
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Protection degreeIP20
Massapprox. 140 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001

Documents: KFA6-STR-1.24.500

Instructions, Short instructions, Safety informationLanguageFile TypeFile Size
System Description Isolated Barriers K-systemENGPDF791 KB
Description du Système pour Barrières Isolées de Système KFRAPDF785 KB
Systembeschreibung Trennbarrieren K-SystemGERPDF782 KB

CAD+CAE: KFA6-STR-1.24.500

CADFile TypeFile Size
Abmessungszeichnung 2D (DXF)/Dimension drawing 2D (DXF)ZIP507 KB
ePLAN-Makros Geräte K-System (EMA)/ePLAN macros K-System devices (EMA)ZIP17983 KB
Abmessungszeichnung 3D/Dimension drawing 3DIGS209 KB
Abmessungszeichnung 3D/Dimension drawing 3DSTP179 KB

Approvals+Certificates: KFA6-STR-1.24.500

CertificatesCert No.File TypeFile Size
Europe Pepperl+Fuchs 2004/108/EC - 2006/95/EC Declaration of ConformityPF 08 CERT 1280PDF360 KB