| Supply | ||
| Connection | terminals 14, 15 | |
| Rated voltage | 90 ... 253 V AC , 48 ... 63 Hz | |
| Power loss | 2.5 W | |
| Output | ||
| Connection | Power Rail or terminals 7+, 8- | |
| Current | 500 mA at 60 °C (140 °F) , permanent short-circuit protection (electronic) | |
| Voltage | 24 V ± 0.5 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Low voltage | ||
| Directive 2006/95/EC | EN 50178:1997 | |
| Conformity | ||
| Insulation coordination | EN 50178 | |
| Electrical isolation | EN 50178 | |
| Protection degree | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Protection degree | IP20 | |
| Mass | approx. 140 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Instructions, Short instructions, Safety information | Language | File Type | File Size |
| System Description Isolated Barriers K-system | ENG | 791 KB | |
| Description du Système pour Barrières Isolées de Système K | FRA | 785 KB | |
| Systembeschreibung Trennbarrieren K-System | GER | 782 KB |
| CAD | File Type | File Size |
| Abmessungszeichnung 2D (DXF)/Dimension drawing 2D (DXF) | ZIP | 507 KB |
| ePLAN-Makros Geräte K-System (EMA)/ePLAN macros K-System devices (EMA) | ZIP | 17983 KB |
| Abmessungszeichnung 3D/Dimension drawing 3D | IGS | 209 KB |
| Abmessungszeichnung 3D/Dimension drawing 3D | STP | 179 KB |
| Certificates | Cert No. | File Type | File Size |
| Europe Pepperl+Fuchs 2004/108/EC - 2006/95/EC Declaration of Conformity | PF 08 CERT 1280 | 360 KB |